Summary
Pole-mounted load-break switch(pole-LBS) applies up to 36kV 400/630A, 50Hz pole-LBS associated with a State-Of-The-Art Controller. This SF6 gas-insulated switch can corporate with the distribution automation system, and also isolate a faulted section of distribution line from the control center.
A simple pole-mounting arrangement contribute to quick and low cost installation, and the switch can be operated manually with a electronic controller. Electronic controller is contained in a stainless steel cabinet for an all weather environmental conditions. Remote monitoring and control can also be provided mounting wire or wireless Modem in a cabinet.
Standard servicecondition
It shall be principal that this SF6 Gas Load Break Switch shall be used in the following service condition;
Ambient temperature
Short period peak value: 50℃ average
Over a period of 24 hours: 40℃ lower
Limit over 24 hours: -25℃ relative
Humidity: 100%
Maximum altitude: 1000 meter
Features
SF6 Gas Insulation
SF6 gas is a nontoxic, non-flame-able dielectric with excellent arc quenching property.
Bushing Versatility
In addition to the standard porcelain bushing, a variety of options are available including elastomeric insulator over epoxy apparatusbushing.
Visible Open/Close
The color coded main contact position indicator(green-open, red-closed) is easily visible from the ground. the indicator is connected directly to the main contact drive shaftass embly assuring accurate contactsstatus.
Quick Operation
Spring charged operator is being utilized compression spring to assure quick make and quick-break operation.
Remote controllable
Electronic controller is available offering local operation or RTU-interface for masterstation control.
Robust Switch
The switch is manufactured from robust, corrosion resistant, proven materials to ensure long service life and also capable of an number of operations which is an ideal characteristic for pole-mounted equipment.
Standard
Every switch is factory filled, hermetically sealed and production tested according to IEC 60265-1(1988) prior to shipment.
Technical data
Descriptions | rating |
rated volatge | 12kV/24kV/36kV |
rated current | 630A |
rated frequency | 50Hz |
rated short-time current | 20KA(r.m.s),4 sec |
rated making current | 50KA(peak), 3 times |
load current breaking | 400/630A,30 times |
cable charging current breaking | 25A,10 times |
line charging current breaking | 1.5A, 10 times |
magnetic current breaking | 22A, 10 times |