++++General:
    VD4 high-voltage indoor vacuum circuit breaker is applicableforthree-phase  AC power system of rated voltage up to 36kV and frequency 50/60HZ,widely used in many fields such as power plant, transformer substation, petrol chemical industry , metallurgy , manufacturing industry , airport, residential area, etc.,to control and protect the electric equipment, especially , It is usedforthe occasionthat needs infrequent operati on at rated current or multi-breaking short circuit current, may be mounted in the indoor air insulating switchgear like type KYN61 or AMS,  ABB type ZS3.2 series, etc. This circuit breaker is made with mature  APG technology . The application of VD4 terminal buffer guarantees the indoorterminal is ever more reliable in nay operation environment. VD4 can fully meet the requirement of GB, DL, IEC, DIN, VDE as well as standards of other advanced industrial countries.
++++Service environment:
    a) Airtemperature: Maximumtemperature: +40℃; Minimumtemperature:-25℃
    b) Humidity: Monthly average humidity 95%; Daily average humidity 90%.
    c) Altitude above sea level: Maximum installation altitude: 2500m
    d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
    e) Nofrequent violent shake
++++ Main technical specifications:


No

Item

Unit

Parameter

1

Rated voltage

kV

36

2

Rated f requency

Hz

50/60

3

Rated current    

A

630, … 2500A

4

1min Power f requency withstand voltage    

kV

95

1 18

5

Lightning impulse withstand voltage    

kV

185

215

6

Rated short circuit breaking current (peak)  

kA

50/63/80

7

Rated short breaking current

kA

20, …31.5

8

Rated short circuit making current (peak)    

kA

50/63/80

9

Rated cable(line) charging breaking current

A

50 and 10

10

Rated single capacitor bank switching current  

A

400

11

Rated withstand current (peak)  

kA

50/63/80

12

Short time withstand current (4s)  

kA

20, …31.5

13

Mechanism life

times

 10000