++++General:
     It is a three phase H.V. switch equipment of 12KV, 50Hz for breaking or closing load current., no-load transformer cable charging current and closing short-circuit current. The load switch with earth switch can bear short-circuit current.
     It is made up of FN12-12D load switch and S()LAJ-12(XRNT()-10) H.V. current-limiting fuse box. It can break any current, load switch breaking working current and fuse box breaking short-circuit current, jointly breaking any current between short-circuit current. Meantime, fuse box make the switch off of with the striker.
++++Service Condition:
     A. The ambient air temperature:  Max.: +40 °C. Min: -10 °C.
     B. The altitude ≤ 1000m.
     C. The relatire humidity of air. daily average ≤ 90%. monthly average ≤ 95%.
     D. The ambient air should not be obviously polluted by corrosivity or the flammability gas and geam. etc.
     E. Without frequent shake.
     F. Enviroment degree: grade Ⅱ.
If requirements are not mentioned above, users can fix them with the manufacturer.
++++Technical Parameter and Performances:
Number  | Name  | Unit  | FN12-12D/630-20  | FN12-12D.R/100-31.5  | 
1  | Rated voltage  | kV  | 12  | |
2  | Rated frequency  | Hz  | 50  | |
3  | Reated current  | A  | 630  | 100  | 
4  | Lighting impulse resisting voltage  | kV  | 75/85  | |
5  | 1min power frequency with stand voltage  | kV  | 42/48  | |
6  | Rated heat - stability current  | kA  | 20(4S)  | |
7  | Rated machine-stability current  | kA  | 50  | |
8  | Rated closing current (peak)  | kA  | 50  | |
9  | Rated short-circuit breaking current  | kA  | 31.5  | |
10  | Rated transfer current  | kA  | 1.5  | |
11  | Max. breaking current  | kA  | 1.8  | |
12  | Breaking no-load transformer capacity  | Kva  | 1250  | |
13  | Rated cable charging current  | A  | 10  | |
14  | Rated power load current breaking times  | time  | >100  | |
15  | Switch-off time of rated power load current switch on-and-off  | S  | >0.06  | |
16  | Earth switch heat-stability current  | kA  | 20(2S)  | 20(2S)  | 
17  | Earth switch heat-stability curreak (peak)  | kA  | 50  | 50  | 
18  | Motor operating power valtage  | V  | AC220,DC48  | |