Indoor fixed type vacuum circuit breaker

Indoor fixed type vacuum circuit breaker

share
  • Detail
  • Parameters

++++General:
    The  vacuum  circuit-breakers  of  type  VD4/S  are  intended  for  indoor  installation  in  air-insulated switchgear  systems.  They  have  a  switching  capacity  capable  of  handling  the  loads  occurring  at start-up and shutdown of equipment and plant units both in normal and in fault state.Vacuum  circuit-breakers  have  particular  advantages  for  use  in  networks  where  there  is  a  high switching  frequency  in  the  working  current  range  and/or  where  a  certain  number  of  short-circuit breaking  operations  are  expected.  T ype  VD4/S  vacuum  circuit-breakers  are  suitable  for autoreclosing, and have exceptionally high operating reliability and long life. The  vacuum  circuit-breakers  of  type  VD4/S,  designed  in  column  form,  can  be  supplied  both  as individualunits for switchgear T ype SM6, Uniswitch, HXGN, etc.
    Standards and specifications
    Switchgear manufacture
    The  switchgear  complies  with  the  following  specifications  in  accordance  with  DIN,VDE  and  the relevant IEC publications:
    • VDE0670, part1000 and IEC60694
    • VDE0671, part100, and IEC62271-100.
    • GB1984-2003
    Installation  and  operation  The  relevant  specifications  are  to  be  taken  into  account  during installation and operation, particularly:
    • DIN VDE0101, Power installations exceeding  AC1 kV
    • VDE0105, Operationof electrical installations
    • DIN VDE0141, Earthing systems for special power installations with rated voltages above1 kV
    •  Accident  prevention  regulations  issued  by  the  appropriate  professional  bodies  or  comparable organizations.
    Operating conditions
    Normal  operating  conditions  Design  to  VDE  0670,  part  1000,  “Common  specifications  for high-voltage switchgear and controlgear standards“ and IECpublication60694, with the following limit values:
    •  Ambient temperature:
    –Maximum +40℃
    –Maximum24 hour average +35℃
    –Minimum (according to “minus5 indoor class”) –5℃
   • Humidity:
   –the average value of the relative humidity , measured over a periodof24 h, doesnot exceed95%
   –the average value of the water vapour pressure, over a period of24 h, does not exceed2,2 kPa
   –the average value of the relative humidity , over a period of one month, does not exceed90%
   –the  average  value  of  the  water  vapour  pressure,  over  a  period  of  one  month,  does  not  exceed  1,8 kPa
  • Maximum site altitude: ≤1000 M above sea level.
   Specialoperating conditions:
   Special operating conditions are to be agreed onby the manufacturer and user . The manufacturer must be consulted in advance about each specialoperating condition:
 • Site altitude over1000 m:
  –Allow for the reduction in the dielectric strengthof the air .
 • Increased ambient temperature:
 –Current carrying capacity is reduced.
 –Provide additional ventilation for heatdissipation.
 • Climate:
 –A void the risk of corrosion or other damage in areas:
 • with high humidity and/or
 • with major rapid temperature fluctuations.
  –  Implement preventive measures (e.g. electric heaters) to preclude condensation phenomena
++++Technical data:

No.  

Item

Unit

Parameters

1    

Rated voltage

kV

12/17.5

24

2

Rated frequency

Hz

   50/60

3    

Rated current

A

630/800/1250/1600

4

1min Power frequency withstand voltage

kV

    38/42/45

50

5  

Lightning impulse withstand voltage

kV

75/95

125/150(*)

6  

Rated short circuitbreaking current (peak)

kA

50/63/80

7

Rated shortbreaking current

kA

  20/25/31.5

8

Rated short circuit making current (peak)

 kA

50/63/80

9

Cable chargebreaking current in earthing fault

A

20

 20

10

Rated withstand current (peak)

kA

50/63/80

11

Short time withstand current (4s)

kA

20/25/31.5

12

Mechanism life

times

  10000

13

Operation sequence



   O-0.3-CO-180S-CO

14

Rateof riseof transient recovery voltage

kV/uS

0.34/0.42

0.47

15


 Peak of transient recovery voltage

kV

20.6/30

41

Guideline values for function times:


No

Item

 Unit

Parameter

1

Closing time approx

ms

60ms

2

Opening time approx

ms

Less than45ms

3

Arcing time (at50Hz)

ms

Less than15ms

4

  Breaking time

ms

Less than 60 ms

Minimum command


5

T ime on closing

ms

 20ms(¹)(120ms(²))

35ms(¹)(70ms(²))

6

Time on opening

ms

20ms(¹)(80ms(²))

20ms(¹)(50ms(²))